4. Water Drainage
4.1 Gradient and Supporting
4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as
possible and eliminate the air bubble.
4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to
keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the prop
stand.
Diameter Distance between the prop stands
Hard PVC pipe 25~40mm 1.5~2m
4.1.3. Precautions
The diameter of drainpipe should meet the drainage requirement at least.①
The drainpipe should be heat② -insulated to prevent atomization.
Drainpipe should be installed before installing indoor unit. Aft③ er powering on, there is some water in
water-receiver plate. Please check if the drain pump can operate correctly.
All connection should be firm.④
Wipe color on PVC pipe to note connection. ⑤
Climbing, horizontal and bending conditions are prohibited.⑥
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.⑦
Heat⑧ -insulation should be done well to prevent condensation.
Indoor units with different drainage type can’t share one convergent drainpipe.⑨
4.2 Drainpipe Trap
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.
4.2.2. Every indoor unit needs one drainpipe trap.
4.2.3. A plug should be designed to do cleaning.
Plug
5
0
c
m
5
0
c
m
4.3 Upwards drainage (drain pump)
For Four-way cassette(compact)